
Download the Delta Controls
Model IPT Datasheet
Note: You will need the Acrobat Reader to view the data sheet.
Features
DESCRIPTION
The Delta Controls Model IPT transmits a 4-20mA signal proportional to the interface position in a water/oil separation vessel. Process conditions can range up to 2500 psig (27 MPa) and up to 500 °F (250°C)
The transmitter sensing probe can be removed from the vessel without disturbing or de-pressurizing the process. The probe is withdrawn up into a chamber located above a block valve. The valve is then closed and only the withdrawal chamber is depressurized. The sensing probe can then be cleaned in place or completely removed.
Applications include refinery desalters, crude oil production separators, reclaimed oil plants, and paper mill soap collection tanks.
MEASURING DESALTER INTERFACE
Measurement of the water/oil interface
position in refinery desalters has commonly been attempted with analog type
capacitance level transmitters. Unfortunately, the measuring probe of this type
device becomes coated with carbon, water emulsions, and other material. This
coating and buildup creates interface position errors and eventually renders
the output signal meaningless. This is true even when a “buildup proof”
unit (as is claimed by some manufacturers) is used. Cleaning the probe and recalibrating
normally restores the signal accuracy. Unfortunately, this mandatory frequent
probe cleaning has not been practical because a pressurized desalter has to
be shut down before this type of continuous transmitter can be removed. A modern
refinery will not tolerate the frequent shutdowns and recalibration expense
required by this type transmitter.
The new Delta Model IPT especially designed probe type interface transmitter
does not require shutdown of the desalter. The sensing probe can be extracted,
cleaned, and reinserted without disturbing operation of the desalter unit. Only
infrequent cleaning of the probe is required. The IPT design allows this infrequent
cleaning to be safely and easily done.
The Model IPT assembly is mounted on top of a desalter isolation valve which
permits its removal without depressurizing the desalter. The sensing probe,
normally inserted down in the process fluid, is withdrawn into a chamber above
the valve whenever access to the probe is desired. The block valve is then closed
beneath it, permitting depressurization of only the withdrawal chamber. The
sensing probe can then be cleaned or even complete removed. The desalter interface
position is monitored by operating the manual try cocks during the cleaning
procedure.

How the Model IPT Senses Interface Position in a Desalter Water/Oil
The percentage ratio of oil/water around the probe determines how energy is radiated away. The energy transfer is at a minimum when it is covered with crude oil and at a maximum when it is covered with water. The Model IPT transmitter is calibrated by locating two interface elevation points in the desalter and pushing a button. The IPT then automatically calculates a curve through those points. The result is a 4-20 mA output signal which is proportional to the elevation of the interface position. This elevation is displayed on the integral LCD screen. The amount of energy flowing is always very small, microamp at millivolt amounts.
Basic Specifications
Go to Delta Controls Home Page
Go to Delta Controls UHF Admittance Type Level Transmitters and Switches
Go to Delta Controls Interface Sensing Level Transmitters and Switches