MODEL
592
MODULAR
CABLE SUSPENDED,
HEAD PRESSURE TYPE LEVEL TRANSMITTER
Download the
Delta Controls Model 592 Detailed Datasheet
Note: You will need the Acrobat Reader to view the data sheet.
Features
- 4-20 mADC signal, 2
wire loop
- Small size is easy to
install. Enters A 3/4" NPT (23 mm) hole, slides easily down a 1"
(27 mm) guide pipe
- Ranges rrom 1 to 2500
feet (0.5 to 780 M) of water
- Support Cable to 4000
feet (1250 m) long
- Unaffected by algae
and wet buildup
- Spark & voltage
surge protection
- Sensor is at the bottom
of well bore or tank
- Electronics in a
remote housing
- Zero and span pots for
recalibration
- Units are field serviceable
- Cable support clamp
provided
- Sludge nose optional
for dirty liquids
- Second vent tube can
check for downhole sealing
- Maintenance free operation
Typical
Applications
Water wells, test wells,
fuel oils, treatment chemical storage tanks, landfill leachate wells, reservoirs,
storm
water retention basins.
Description
The Delta
Controls Model 592 electronics unit is separated from the sensor and
mounted above ground for ease of testing, recalibration, and inspection. The
sensor is mounted in a heavy 316 S.S. body. A rugged electrical cable interconnects
them and supports the body. Both are potted for maximum reliability. The sensor
measures the pressure of the liquid above it. This pressure is linearly proportional
to the height and density of the liquid above it. The Model 592 converts this
pressure into a 4-20 mADC level signal. The sensor is connected through a vent
tube to atmospheric pressure for a reference.
Unlike capacitance
and admittance type devices, the Model 592 is unaffected by algae
and sludge coating. Also, its calibration can be checked or changed without
the unit being installed in a well or pit.
The Delta Controls Model
592 is also very useful for measuring levels in tanks. The flexible cable is
easy to install, even when head room above a tank is minimal. The small body
diameter allows it to be installed through a 3/4" MPT hole. Use the TPC
corrector to compensate for gas space pressure option when the tank is pressurized.
Specifications
- Technology:
Silicon strain gage
- Supply
Power: 13 to 35 VDC
2 wire loop powered
- Output Signal:
4-20 mADC, isolated, intrinsically safe
- Loop Impedance:
550 ohms at 24 VDC,1100 ohms at 35 VDC
- Adjustments:
Span from 30% to 100% of range, zero to 30% is basic, non-interactive.
- Over Pressure:
2X Range, 35 PSI (2.5 Bar) minimum without damage; 3X Range, 1000 PSI
(70 Bar) minimum without rupture
- Vent Tube: Protected
from moisture condensation through a desiccant filter or isolation bladder
- Temperature
Range:
- -20 to +220°F Operating
- -40 to +275°F Intermittent
- 30 to +130°F Compensated
(Higher Available)
- Accuracy:
± 0.25% F.S. or better
- Thermal Error:
± 0.02% F.S. / °F maximum
- Barometric Effect:
None
- Weight:
- Transmitter, less
than 1 pound (0.5 KG)
- Cable, 1 pound per
25 feet (0.5 KG/8M)
Optional
Features
- Indicator:
Large integral direct reading LCD
- DC Power Supply:
Integral VAC to 24 VDC
- Alarm and Pump
Control Module(s): Integral 5 amp, SPDT
- Liquid Temperature:
Is sensed and transmitted as a 4-20 mADC signal over a second 2 wire loop.
Third Party
Approvals
- CSA (Canada)
- NRTL/C (USA)
- Intrinsically safe
- Environment proof
- Sanitary (Worldwide)
- ISO-9001 Quality System
Go to Delta
Controls Home Page

<592>